Splash / Trickle Fills
- Products suitable for inferior water qualities
- High security against blockages
- Chemical and high temperature resistance of Polypropylene
- High stability
- Cleaning with high pressure cleaners possible
- Long service life
- Environmentally friendly
Technical Data
| Type |
FC20.30 |
FC70.34 |
NET 150
NF20-R |
| |
 |
 |
 |
| Material |
PP |
| Geometric surface area m2/m3 |
110 |
-- |
80 |
| Effective surface area m2/m3 |
110 |
-- |
up to 130 |
| Corrugation height mm |
30 |
-- |
20 |
| Length mm |
600 |
1000 |
905 |
| Width mm |
1200 |
500 |
604 |
| Height mm |
150 |
45 |
450 |
| Spacing of supports mm |
300 |
250 |
800 |
| Width of supports mm |
15 |
25 |
50 |
| Max. application temp. °C |
80 |
| Void ratio % |
> 97 |
| |
|
|
|
Typical Applications
|
|
|
|
| Cooling Tower |
Polluted water
counter flow only |
Strongly polluted water
counter flow only |
Polluted water
counter and cross-flow |
| Water Treatment |
CO2-Stripping |
-- |
-- |
| Waste Water |
-- |
-- |
Submerged biofilm reactors |
| Mass Transfer |
-- |
-- |
Counter and cross-flow
scrubbers |
This information has been put together with greatest care. However, any performance data given on this page is subject to compliance with certain surrounding conditions and hence may vary from case to case. Further, we reserve the right to make changes at any time without notice. We strongly recommend (i) reconfirmation with GEA 2H whether this information is still fully valid, before using it for final designs and (ii) to verify performance data taking into account the actual surrounding conditions. GEA 2H takes no responsibility for any consequences due to non-compliance with these recommendations.
|
|
|
|